Control circuit connection and operation – GE Industrial Solutions AF-300C AC Drive User Manual

Page 65

Advertising
background image

AF-300C

GEK-85718

CONTROL CIRCUIT CONNECTION

AND OPERATION

Basic connectlons that are required for operation

from the Keypad Panel are shown in Figure 5-6 (this

is a factory installed jumper).

A wiring example of commonly used signals that

are optional for either Keypad Panel Operation or
External Operation (through control circuit terminals)
is shown in Figure 5-7.

Connection description is as follows:

308, 30C Fault Relay Output used for

alarm circuits, etc.

FM2 Used for external analog meter

when frequency indication is needed.

-- THR Connected to CM terminal at factory.

-- BX Connects to a normally open contact.

When motor coast stop is desired during nor-

mal operation, close this contact and remove

the RUN command (FWD or REV).

Termlnal Connectlons required for operatlon from

Keypad Panel are shown in Figure 5-8.

Operation is as follows:

-- Rotation Direction Press

on the Keypad

for forward rotation or REV on the Keypad for

reverse rotation.

-- Frequency Setting The frequency reference

can come into the inverter in one of the follow-

ing ways when the LOCAL/REMOTE switch is

in the ‘LOCAL’ position.:
1. Set the motor speed by pressing the IN-

CREASE SPEED or DECREASE SPEED kevs

Connects to a normally closed contact. When
inverter STOP is desired through external alarm,

on the Keypad Panel to increase or de-

open this contact. The inverter will trip on

crease the inverter output frequency.

and the motor will coast stop.

2. Multi-Step Speed Settings can be selected

by terminals

X2, and X3. (Program-

-- RST -Connects to a normally open momentary

mable preset frequencies in the Function

contact for resetting a fault externally.

Codes can be selected.)

-- See Figure 5-9 for RUN Operation example.

C

l

X

3

L v

B X

l

l CAUTION: it is desired to use thermal interlocks, remove the

jumper from between terminals THR and CM, and connect nor-

mally closed thermal interlock contacts in series between THR
and CM.

r

5-6. FACTORY CONNECTIONS

: If it is desired to use thermal interlocks, remove the

between terminals THR and CM, and connect

thermal interlock contacts in series between THR

r

Figure 5-7. EXAMPLE OF COMMONLY USED SIGNALS

5-l 1

Advertising