Continued), Table 7: fault description and operation – GE Industrial Solutions AF-300C AC Drive User Manual
Page 94
GEK-85718
TABLE 7: FAULT DESCRIPTION AND OPERATION
(continued)
Function
OH2 External Fault
Err0
CPU Abnormal
Err9
Setting Error
Err2
Setting Error
Errd
Error
Stall Prevention
input Surge
Description
When the overtemp detection device of the brake unit and brake resistor
(optional) or the user’s external thermal relay is activated, the inverter will
stop output and hold the fault trip (motor coasts to stop).
If the inverter CPU operation is abnormal, the inverter will stop output and
hold the fault trip (motor coasts to stop).
When low limit frequency setting exceeds that of the high limit frequency.
When a Function Code that cannot be set while inverter is running has been
attempted to be set.
Stored setting data is abnormal. This error message cannot be reset.
Replace the Main Control Card.
NOTE:
may be possible to c/ear this condition by removing and
reinserting any socketted integrated circuit chips on the Main
Card
of three).
Automatically extends acceleration time to restrict overcurrent during rapid
acceleration (to prevent overcurrent trip).
Automatically extends deceleration time to restrict overcurrent and over-
voltage during rapid deceleration (to prevent overcurrent and overvoltage
trip).
The inverter can be protected from
standard impact wave voltage which
will invade from the main circuit power.
8-2