GEK-85718

TABLE 7: FAULT DESCRIPTION AND OPERATION

(continued)

Function

OH2 External Fault

Err0

CPU Abnormal

Err9

Setting Error

Err2

Setting Error

Errd

Error

Stall Prevention

input Surge

Description

When the overtemp detection device of the brake unit and brake resistor

(optional) or the user’s external thermal relay is activated, the inverter will

stop output and hold the fault trip (motor coasts to stop).

If the inverter CPU operation is abnormal, the inverter will stop output and
hold the fault trip (motor coasts to stop).

When low limit frequency setting exceeds that of the high limit frequency.

When a Function Code that cannot be set while inverter is running has been
attempted to be set.

Stored setting data is abnormal. This error message cannot be reset.

Replace the Main Control Card.

NOTE:

may be possible to c/ear this condition by removing and

reinserting any socketted integrated circuit chips on the Main

Card

of three).

Automatically extends acceleration time to restrict overcurrent during rapid

acceleration (to prevent overcurrent trip).

Automatically extends deceleration time to restrict overcurrent and over-
voltage during rapid deceleration (to prevent overcurrent and overvoltage
trip).

The inverter can be protected from

standard impact wave voltage which

will invade from the main circuit power.

8-2