Table 4: keypad and display operation – GE Industrial Solutions AF-300C AC Drive User Manual
Page 56
FUNCTION
DATA
Figure 5-1. KEYPAD PANEL COMPONENT
TABLE 4: KEYPAD AND DISPLAY OPERATION
LED indicator -The LED indicator is made up of
three sections as follows:
Function Code Display-Displays in two digits
the selected Function Code number. LED
Selection Indicator under each digit lights when
that digit is selected to be changed.
Data Display Display in four digits the operation
data, Function Code setting data, and the fault
codes.
Unit Indicator -The LED on the left of each unit
symbol corresponds to the contents of the
data display.
NOTE: All letters are displayed in upper case
except
and
Touch Kevs There are eleven Touch Keys and
one switch that perform as follows:
SHIFT Key Selects the Function Selecting Mode
and the Parameter Setting Mode.
-- The order of selecting each digit is fixed as
2nd Function digit 1st Function digit Data
digits in sequence, except the order is 2nd
Function Digit st Function digit for Function
Codes 00-05,
and
(see Figure
-- When the data on the Data Display is blinking,
you cannot change the selection by pressing
the SHIFT Key. Press the RESET key to
recover original data and stop the blinking or
press the SET key to store the newly changed
data and stop the blinking. The SHIFT key
can then be used to make the selection.
5-2