2. Set all operating switches to OFF and set

Remote’ switch to

position.

3. Apply AC power.

-- Control circuits and sequence circuits will be

activated and charge LED will light.

-- Data Display portion of

Panel will

blink

while the CPU is checking the

internal data.

ceases to blink while CPU is checking

that Function Code set data matches the speci-
fication.

--

Panel will display last operation mode

of invetter prior to removal of AC power.

4. Use “Increase Speed” or ‘Decrease Speed’ keys

to set desired reequency. (A low frequency of

about 5 Hz is recommended for the first run.)

5. Give a Forward or Reverse command and check

for the following: (See Figure 5-5.)

-- Correct direction of rotation.
__ Smooth rotation of motor.

Any abnormal vibration or noise in the motor.

-- Smooth speed increase and speed reduction.

6. Check for any abnormal heating, fumes, etc. while

motor is rotating.

7. Perform the following using the Keypad Panel:

__ Raise the reference frequency gradually and

verify that it reaches top frequency for the

particular application (typically 60 Hz, default

setting from factory).

Check AC motor current (should be approxi-

mately 3040% of rated current with no load).

__ Lower the reference frequency and stop the

motor.

8. Reconnect any equipment disconnected in step

of this procedure.

9. Perform steps 5 thru 7 with the load connected.

NOTE: any Function Code settings need to be
changed, refer to ‘Setting Function Codes’ paragraph

in this Section.

OUTPUT

Figure 5-5. ELECTRIC MOTOR ROTATION