AF-300C NON-HORSEPOWER
OPTIONS
Description
GE Catalog #
Card
BCD Card
Amps Signal Card
Output Signal Card
Pulse
Feedback Card
Description
GE
Relay Unit
Keypad Cable 2M
Speed Potentiometer
Reactor
CAUTION:
The AC Power
Transformer KVA
should be
than 1.5 times the HP
of
the Inverter, but not greater than 10 times the HP ratinq of the lnverter or 500 KVA (whichever is
If an
AC Power
Transformer
than this is to be used, install a Line Reactor
be purchased
on the line side of the Inverter. A Line Reactor is also required if an
controller and/or power
factor correction capacitors are used on the same power lines.
AC LINE REACTORS FOR
AF-300C
(See Caution)
200 460
232
295
75
250 460
287
370
50
300 460
316
400
50
*
For input voltages other than 460, Contact General
Electric Company, Drives Products Operation.
Amps shown are at 460 VAC input voltage.
***AC Line Reactors may also be required for
rated
UP and above even though a DC Link reacfor is
provided with the inverter.
NOTE: If reactors are supplied by others, be sure that the
peak (non-saturating) current rating of the reactor is greater
than 2.8 times the input current rating of the inverter.