AF-300C NON-HORSEPOWER

OPTIONS

Description

GE Catalog #

Card

BCD Card

Amps Signal Card

Output Signal Card

Pulse

Feedback Card

Description

GE

Relay Unit
Keypad Cable 2M
Speed Potentiometer

Reactor

CAUTION:

The AC Power

Transformer KVA

should be

than 1.5 times the HP

of

the Inverter, but not greater than 10 times the HP ratinq of the lnverter or 500 KVA (whichever is

If an

AC Power

Transformer

than this is to be used, install a Line Reactor

be purchased

on the line side of the Inverter. A Line Reactor is also required if an

controller and/or power

factor correction capacitors are used on the same power lines.

AC LINE REACTORS FOR

AF-300C

(See Caution)

200 460

232

295

75

250 460

287

370

50

300 460

316

400

50

*

For input voltages other than 460, Contact General
Electric Company, Drives Products Operation.

Amps shown are at 460 VAC input voltage.

***AC Line Reactors may also be required for

rated

UP and above even though a DC Link reacfor is

provided with the inverter.

NOTE: If reactors are supplied by others, be sure that the
peak (non-saturating) current rating of the reactor is greater

than 2.8 times the input current rating of the inverter.

2-10