AF-300C

GEK-85716

Motor Runs But Speed Does Not Change

NO

Is Upper/Lower Limiter

Activated?

(Function Codes

14

NO

Use INC SPEED and

What position is the

LOCAL/REMOTE switch

on the Keypad in?

LOCAL

REMOTE

Are Xl, X2, X3

.

DEC SPEED Keys On

Keypad To Change

Speed

Are Function

terms.

Codes 41 and 42

to CM?

set correctly?

NO

Correct Wiring Error.

Is 11,

Cl,

NO

Wiring Correct?

Are All Frequency

Correct Function

YES

Settings Different?

Code Settings.

YES NO

Analog Frequency NO

Do Voltage And

Change Frequency

Setting Device Failure.

Current Inputs To

Settings.

Vi, 12, or

Change?

I

Use

X2, X3 terms.

YES

to select frequency.

Are Acceleration/

Deceleration Times

Too Long?

NO

YES

Adjust Acceleration/

Deceleration Time

To Match Load.

lnverter Problem.

Figure 8-1. “MOTOR RUNS BUT SPEED DOES NOT CHANGE“ TROUBLESHOOTING CHART

8-5