Alarm Reset Switch Connection

If an external RESET is required, connect a momen-

tary pushbutton to the RST terminal as shown in

Figure 4-10.

NOTE: The application of this terminal allows a

parallel operation to be performed with the

on the Keypad Panel. Carelessness when setting
Function Codes and/or retrieving faults
may result in

inputting a RESET signal.

Equivalent Control Circuit

The equivalent circuit as shown in Figure 4-11 is pres-

ent in the control circuits (FWD, REV, BX, THR, RST,
PU, IL,

X2, X3,

, RT2,

The contacts used

must be highly reliable contacts for low voltage sig-
nals. 24 VDC is present when the switch is open; 3

DC is present when the switch is closed. The

maximum leakage current that can be tolerated and
still maintain an OFF state is 80

The maximum

voltage drop that can be tolerated and still maintain

an ON state is one volt.

Flgure

1. EQUIVALENT CONTROL

Fault Relay Contact Rating

The Fault Relay contacts are rated at 250 VAC, 300

milliamps inductive cos 0.3. When a large MC

Contactor is used, use a pilot relay with the appropri-
ate contact rating and coil rating. (See Figure 4-12.)

Open Collector Output Terminal Connection

It is recommended to use the optional relay output
unit when using these output signals, however it is
possible to use a customer furnished power supply
and relays. The open collector outputs are “sink

circuits. If customer supplied relays are to be con-

trolled, an external DC power supply (27 VDC max.) is

required. A diode must also be installed (reverse
biased) for relay coil suppression (see Figure 4-13).

CAUTION:

that the

of the power

supply connections are correct. Damaue will occur if

RESET

SWITCH

Figure

0. FAULT RESET CONNECTION

,

.

supplied.

Figure 4-12. FAULT RELAY CONTACTS

THAN

UP TO

(CUSTOMER

SUPPLIED)

Figure 4-13. OPEN COLLECTOR CONNECTION

4-8