TABLE 8: FAULT CONDITION DISPLAY AND

CORRECTIVE ACTION

Check For:

Corrective Action

AC supply voltage not within permissible limits . . . . . . . . . . . . Check inverter specs and adjust AC supply voltage.
Output line short-circuited . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Check output line insulation.

Megger test the motor.

Proper torque boost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Adjust as needed (reduce torque boost).

Proper acceleration time

Lengthen the acceleration time.

Loose Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Check on operation of external output contactor

If used.

Check Main Circuit wiring connections

Other than above

Check transistors

Increase inverter capacity (use larger HP inverter).

AC supply voltage not within permissible limits . . . . . . . . . . . . Check inverter specs and adjust AC supply voltage.
Output line short-circuited . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Check output line insulation.

Megger test the motor.

Proper deceleration time

Lengthen the deceleration time.

Loose Connections

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Check on operation of external output contactor
If used.
Check Main Circuit wiring connections

Other than above . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Connect DB braking unit resistor (optional) or check
operation of if already present. (Check

of

thermal interlock connections to DB unit.)

Increase inverter capacity (use larger HP inverter).

o c 3

AC supply voltage not within permissible limits . . . . . . . . . . . . Check inverter specs and adjust AC supply voltage.
Output line short-circuited . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Check output line insulation.
Megger test the motor.

Sudden change in load

Eliminate sudden load changes.

Loose Connections . . . . . . . . . . . . . . . . .

. Check on operation of external output contactor

if used.
Check Main Circuit wiring connections

Other than above . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Check for electrical noise.
Check on operation of external output contactor

If used.

Increase inverter

(use larger HP inverter).

ou

AC supply voltage not within permissible

. . . . . . . . . . . . Check inverter specs and adjust AC supply

voltage.

Proper deceleration time

Lengthen the deceleration time.

Dynamic Braking not functioning properly

Connect DB braking unit resistor (optional) or check
operation of if already present.
Check polarity of thermal interlock connections to

DB unit.
Check Function Code 34; increase setting

value if

necessary.

NOTE: Motor will coast-to-stop when fault condition is displayed. After obtaining Fault information and correcting the

cause of the problem, reset by pressing the RESET key on the Keypad Panel, or momentarily close contact between the

control circuit terminals after the motor has stopped.

NOTE: if a fault cannot be reset, check to be sure that a RUN command is not present.

NOTE:

may be displayed when the AC supply is switched OFF and does not indicate any abnormality.