GE Industrial Solutions AF-300C AC Drive User Manual

Page 77

Advertising
background image

GEK-85716

Function A Automatic Energy Saving Oper.

When automatic energy saving operation is se-

lected, voltage is reduced as shown. The voltage is

decreased as the load current decreases.
0

= Active
= Inactive

voltage

Function 1 b Electronic Thermal Overload

I

Electronic thermal setting should be made with the

following equation:

Electronic Thermal Overload =

Rated electric motor current

x 100%

Rated inverter current

--When using a 4 pole, 3 phase motor, the motor

can be protected from overload without an exter-
nal thermal relay.

-- The electronic thermal calculation compensates

for a decrease in motor cooling at low speed .

--When using one inverter with more than one

motor, an external thermal overload relay should
be used for each motor.

-- lfthe

Function is not used, set

at 0%.

CAUTION:

The electronic thermal overload

meets the reauirements of

standard

motors onlv. When anv of the followina conditions
exist, use conventional overload

instead of

the electronic overload built into the inverter.
-- Motors other than

Special motors (anv non-standard motor).
For a

where two or more motors

are run

a

inverter.

--

has frequent

-- Operation is at

Hz or less.

3 0 %

Threshold Where Timing Begins Based

On Output Frequency And Current,

And Electronic Thermal Overload Setting

Time

Before

Trip

(Min.)

Output Current

Inverse Time Characteristic with

Electronic Thermal Overload = 105%

6-3