GEK-85718

Adjustment of Upper/Lower Limits

Function 14 High Output Freq. Limiter
Function 15 Low Output Freq. Limiter

The upper and lower limiters can be set so that the

inverter output frequency will stay within these
limits.

will prevent motor overspeed and

speed.

NOTE: If the High Limit is set lower than the Low

Limit, the Low Limit will be ignored and an error in-
dication

will be displayed.

0 to
0 to

time setting

I)

Function

Acceleration Time

Function 17 Deceleration Time

The acceleration and deceleration times define the

amount of time it takes between 0 Hz and

t

: 0.2

to 3600 seconds

t

: 0.2

to 3600 seconds

Function 18 Frequency Gain (Gain)

I

The frequency gain adjustment can be used to

scale the analog voltage reference at the top end.

Gain: 0 to 200%

When the freauencv setting

is applied with a

current input, this function cannot be used.

Function 19 Torque Boost

I

21 patterns can be selected

boost = 0 to 20).

-- Patterns (0) and (1) are used for low torque loads

(available for fans and blowers, thus improving

characteristics such as vibration, noise, and effi-
ciency.

-- Pattern (2) is characteristic of V proportional to

the square of f up to

-- Pattern (3) is characteristic of constant V/f up to

-- Patterns (4) through (20) are to increase V/f in a

low frequency range between 0 to

to

make up the torque at low speed operation and

to give torque boost characteristics.

Torque Boost: 0 to 20