GE Industrial Solutions AF-300C AC Drive User Manual
Page 82
Frequency Monitor
Function 40 Pulse Freq. Meter Coefficient
Function 50 Analog Freq. Meter Calibration
The inverter output frequency can be monitored
from terminals FM1 (+) and FM2
Set Jumper
the Main Control Card in the
position for
an analog meter or in the
position for a pulse
type meter.
Function 41
Command Hold (3-wire)
This function enables control by a one-shot (50ms
minimum) RUN/STOP command (FWD and REV
command), External self-sealing circuits can be
omitted.
When this function is selected, multi-step speed
settings from 1 to 3 can be used, but those from 4
to 7 cannot.
NOTE:
commend hold, no other commands
will be received
a STOP command is given.
Active:
control, momentary contacts)
Inactive:
control, maintained contacts)
Function 42 Up-Down Control Selection
The frequency can be increased and decreased
using terminals
-CM and X2-CM. This function
simulates a motor driven potentiometer.
In addition, if power is shut down, set value is
stored. When operation is started again, inverter
will come up to the stored frequency.
NOTE: The functions of multi-step frequency,
sealing selection, and up-down control use the
same terminals. Thus, there are four possible
combinations of operation.
three functionsca
nor be used
n
6 to 100
Pulse Period =
(sec.)
f =
Freq.
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
o Analog output
Calibration
Output
Range:
voltage
1 0 5 %
o v
o u t p u t
100%
frequency
Pulse
Signal Width
be 60 msec. or longer
NOTES: When this control function is selected, multistep
speed setting 4 (Function Code 26) can be used, but
the other six settings cannot.
Multi-Step Speed Setting,
Command Hold,
and Up-Down
cannot be usedsimultaneously
because the same terminals are used for these func-
tions.
If the Up-Down function is selected, external
setting signals (voltage and
are
gored.
If Up-Down buttons are pressed at
same time,
down will take precedence.
Act.
Up-down control
Comm-hold sel.
6-8