GEK-85718

Motor Rotation Is Not Smooth

During Acceleration/Deceleration?

NO

Lengthen Acceleration/Deceleration

Time Setting.

Y E S

Input Voltage Fluctuation?

Correct Power Line Problem.

NO

Large Load Fluctuation?

NO

YES

Increase Motor And lnverter Capacity.

Attach A Flywheel.

YES

Noise Interference In Analog Input?

Test With Analog Frequency Setting Device.

lnverter Problem

Figure 8-2. “MOTOR ROTATION IS NOT SMOOTH” TROUBLESHOOTING CHART

Motor Overheats

NO

Do Motor And V/F Pattern Match?

YES

Correct

Pattern Setting

(Function Codes 10, 11, and 12).

Is There Continuous Low Speed Operation?

YES

Use Special lnverter Motor. Lower The Torque

Boost (Function Code 19).

Is The Load Too Heavy?

YES

Reduce Load. Increase lnverter Capacity

(Use Larger HP Inverter).

Check lnverter Output Voltage Balance.

I

YES

If Good, Indicates Motor Problem.

NO

If Not Good, Indicates lnverter Problem.

I

Figure 8-3. “MOTOR OVERHEATS” TROUBLESHOOTING CHART

8-6