Auxiliary function codes – GE Industrial Solutions AF-300C AC Drive User Manual

Page 78

Advertising
background image

AUXILIARY FUNCTION CODES

Functions

47

DC Brake

Function 20 DC Brake Start Frequency

Function 21 DC Brake Voltage

Function 22 DC Brake Time

Brake Start Freq.:

0.0, 0.5 to 60 hz.

Brake Voltage:
Brake Time:

0 to

seconds

Brake Duty Cycle:

5% maximum

The DC brake is applied when

command is

given and the inverter output frequency is at or

below the DC brake start frequency.

-- If the motor/load inertia is so large that the rota-

tion is not stopped aftertheset DC brake time (10
seconds maximum), the motor/load will coast

until stopped.

-- When DC brake is not used, set the Brake Start

Frequency to

Frequency Setting Selections 7

Function 23 Multi-Step frequency 1
Function 24 Multi-Step frequency 2 (MSS2)
Function 25 Multi-Step frequency 3 (MSS3)
Function 26 Multi-Step frequency 4 (MSS4)
Function 27 Multi-Step frequency 5 (MSS5)
Function 26 Multi-Step frequency 6
Function 29 Multi-Step frequency 7

External contact signals allow a selection of seven

x 2 - w

speeds.

Each step speed can be set between 0.5 and 400
HZ.

The rate of change of the output frequency be-
tween each step is adjustable by the
time setting.

NOTE: Multi-step frequency

overrides

frequency reference signals.

Relationship Between Terminals and

Multi-Step

1 to 7

Fun. Code

off

On On Off Off On Or

off

Off Off On On On Or

4

6-4