GE Industrial Solutions AF-300C AC Drive User Manual

Page 63

Advertising
background image

4.

5.

Press the UP or DOWN ARROW keys to set the
desired number (F5, F6, F7). (See Figure
-- Each fault history will be shown on the Data

Display when selected.

Press RESET key to return to Operation Monitor-

ing mode (no ‘move up’ of fault history will occur).

DATA PROTECTION

Function Code data can be protected against acci-
dental changes by the setting of Function Code 99.

When data is ‘Protected’, it cannot be changed until

Function Code 99 is changed

There

are two different methods of setting the data protec-

tion. Perform either of the following procedures that

best suits your particular application.

OPERATION PROCEDURE

To Set Protection:

-- Function Code Display will display

with

neither of the Function Selection

lit.

Press FAST key first and then SET key (while
FAST key is still depressed) to set Function Code

99 to ‘Protected’.

Data Display will show (0) in the first digit posi-

tion to indicate ‘Protected*. (This will be dis-

played for approximately 5 seconds after keys

are released.)

-- Data Display will then return to its previous

mode.

-- All Function Code data currently set will be pro-

tected.

To

Release

Protection:

Press FAST key first and then RESET key (while
FAST key is still depressed) to set Function Code
99 to “Unprotected’.
-- Function Code Display will display ‘99” with

neither of the Function Selection

lit.

Data Display will show in the first digit posi-

tion to indicate ‘Unprotected”. (This will be dis-

played for approximately 5 seconds after keys
are released.)

Data Display will then return to its previous

mode.

All Function Code data currently set will no

longer be protected.

GEK-85718

OPERATION PROCEDURE

1.

2.

3.

4.

5.

6.

Press SHIFT key until Function Selection Led
under the second digit of Function Code Display is
lit.

-- This selects the second digit.

Press UP or DOWN ARROW keys until

is dis-

played in the second digit position.

First digit of Function Code Display will auto-

matically be set to

also.

Current status of “Protected’ (0) or ‘Unpro-

tected”

will be be displayed in the first digit

position of the Data Display.

Press SHIFT key to advance to

Mode.

Both Function Selection

will go out.

Press UP ARROW key to set to “Protected” status.
-- (0) will be displayed in the first digit position of

Data Display.

or

--

will be displayed in the first digit position of

Data Display.

Press DOWN ARROW key to set to “Unprotected
status.

Press SET key to store selection into memory.

Press RESET key to return to Operation Monitor-
ing Mode.

TRIAL KEYPAD OPERATION (Optional)

Before trial

of the inverter, ensure that all

inspections outlined in the “Before Applying AC Power
Inspections’ paragraph have been performed.

WARNING MECHANICAL MOTION

HAZARD:

When

from the Keypad Panel

wlth the “Local/Remote” switch In

tion, presslng the FWD or REV key

cause the

motor to rotate. Any RUN permissives that may be

wired to the FWD or REV termlnals are Ignored.

If a test run Is desired, run the inverter at a low fre-
quency of around 5 Hertz. Conduct

operation

per the following procedure:

1. Disconnect all couplings and belts that connect

the electric motors and machinery so as to allow

independent operation of the electric motors.
-- If the electric motors are connected directly to

the machinery, verify that any mechanical motion
will not pose a safety hazard.

5-9