How to Manually Tune the Control Loop

MTS Series 793 Tuning and Calibration

Tuning Procedures

81

Note

You can also use the optional Scope or an external oscilloscope to adjust
I Gain by monitoring the Error signal. For more information, see

“How to

Use Error to Tune I Gain”

on page 102.

11. Save your tuning settings.

Standalone FlexTest SE Controllers: Setup > Open/Save Parameters >
<<Save>>

Automated Controllers: On the Station Manager File menu, select Save
Parameters As
.

You can either select an existing parameter set or enter the name of a new
parameter set to save.

About saving elements

of a parameter set

It is important that you save your parameter set as you complete the various
parts that make up a parameter set. Throughout this manual you will be
performing discrete procedures while building a single parameter set.

If you have already established your default parameter set for the
current station and you are creating a new parameter set for a specific
test, save the parameters with a different name.

Different tests and/or specimens may require different parameter sets.