MTS Series 793 Tuning and Calibration

How to Perform Advanced Tuning Techniques

Tuning Procedures

98

10. Create a program with the function generator application.

Standalone FlexTest SE Controllers: Select FG and select the following
settings to set up a tuning program.

Automated Controllers: In the Station Manager window’s navigation

pane, click

.

11. Start the function generator

Standalone FlexTest SE Controllers: Press Run to start the displacement
command.

Automated Controllers: In the Station Controls panel, click

to start

the Function Generator.

12. Observe the spool position signal on the Scope.

If the Spool Position signal is too small to be properly displayed on the
Scope window during tuning, increase the Function Generator panel’s
Amplitude.

If the Amplitude setting does not amplify the spool signal as expected,
increase the P Gain.

Standalone FlexTest SE Controllers: Tuning > P Gain

Automated Controllers:

A. In Station Setup window’s navigation pane click

.

C

ONTROL

S

ETTING

Type

Cyclic

Wave Shape

Square

Control Mode

displacement

Target Setpoint

0 mm

Amplitude

50% of full scale

Frequency

1 Hz

Compensator

None