UPS Input/Output

This input changes state when the UPS normally open Low
Battery contacts open to indicate that UPS battery power is

UPS Low Battery (Digital
Input 2)

low (regardless of whether the UPS is supplying power to the
system or not).

Only supported in systems that use a Model 493.73 HPU
board.

UPS External Event (Digital
Input 3)

Not Used.

UPS Off (Digital Output 1)

b) Define the State, Persistence, and Polarity settings for each UPS input.

Description

UPS Setting

The State setting is locked in the Enabled state.

State

Future - Determines whether or not the line fault detector changes state
if power is supplied by the UPS. The default setting is Enabled.

Time value in milliseconds. This is the number of milliseconds in which
the state must persist before the software recognizes the change. The

Persistence

default setting is 0, which means the change in state is recognized
immediately.

Normal or Inverted. The default value depends on the type of hardware
resource used to monitor the UPS:

Polarity

For Model 494.44 and Model 494.42 system boards: Default = Normal

For Model 493.73 HPU boards: Default = Inverted

These default polarity settings are based on normally open contacts.

3. Define Station UPS Options with the Station Manager application.

When you open a station configuration created with an .hwi file that includes a UPS, you can
select UPS options in the Station Setup window.

For more information on , see the Series 793 Control Software manual (PN 100-147-130).