High Speed Data Acquisition Settings

Each Series 494 DUC has a High Speed Data hwi setting that is used to enable high-speed data
acquisition.

Note:

High-speed data acquisition is required for some applications (for example, the MPT High
Speed Timed Acquisition process).

High-speed data limitations

The Model 494.40 I/O Carrier board allows up to six high-speed data inputs per carrier board. This
could be an issue if four Model 494.26 Dual DUCs are installed on a 494.40 I/O carrier.

Description

Setting

Enables high-speed data acquisition. The high-speed rate is
determined by the system rate and a number of other factors.

True

See your test application documentation for details.

High-speed data acquisition is not available.

False (default)

Model 494.16 VD/DUC HWI Settings

Description

Item

Describes the valve driver/DUC mezzanine card.

494.16 VD/DUC mezzanine
card icon

Application Attribute: Not applicable

Type: defines how the card is used and what resources are available.

DUC and 2SVD: when configured as a two-stage valve driver,
the DUC portion of this card is available as a system resource.

3SVD: when configured as a three-stage valve driver, the DUC
portion of this card is reserved for the valve LVDT.