MTS Series 793 Utility Software User Manual

Page 54

Advertising
background image

Description

Item

Off/high: two HPU control buttons (Off/High) will appear on the Station
Manager Station Controls panel.

First On:

False: Setting First On and Last Off to False allows the HPU to
operate independent of HSM controls.

True: Setting First On and Last Off to True allows HSM Low selection
to activate HPU High without pressing the HPU buttons. (The first
HSM turned on activates the HPU.)

Last Off: True: Causes the last HSM turned off to turn off the HPU.

The First On/Last OFF settings are only available if the HPU with
HSM setting is True.

Visible:

True: Indicates whether or not the HPU button is visible on the control
panel.

False: hides the HPU button display on the Station Manager window
(only if both First On and Last Off are True).

The Visible setting is only available when both the First On and First
Off settings are set to True.

Connector: J28A or J28B

Hydraulic Interface icon
(HSM)

Name: Describes the hardware resource as it will appear in Station
Builder resource lists.

Changing this name may invalidate existing station configurations.

Interlock: 1 (default for J28A ), 2 (default for J28B).

(Should this be read only?)Type: Solenoid, Proportional, On/Off
Solenoid.

Solenoid: three HSM control buttons (Off/Low/High) will appear on
the Station Manager Station Controls panel.

On/Off Solenoid: only two HSM control buttons (Off/On) will appear
on the Station Manager Station Controls panel.

Proportional: configure the proportional output with the controller
software. The output signal can be ramped from 20 mA (minimum)
to 700 mA (maximum) which corresponds with 50 psi (0.4 MPa) and
3000 psi (21 MPa). By default, low pressure is factory set at 750 psi
(5.25 MPa) and high pressure is set at 3000 psi (21 MPa).

Low Percent: 25. HSM low pressure setting as a percentage of
full-scale.

High Percent: 100. HSM high pressure setting as a percentage of
full-scale.

HSM Rate: Slow = 4 seconds. Fast = 2 seconds.

40 MTS Series 793 Utility Software

HWI Hardware Settings