Model 494.42 Single-Station System Board Settings

The Model 494.42 board is used with FlexTest 40 controllers.

Description

Item

The System Board defines digital and analog inputs and
outputs, and hydraulic power unit (HPU) and hydraulic
service manifold (HSM) functionality.

494.42 System Board circuit board icon

Slot: 4.

Properties tab

Slot 4 in the FT-40 chassis is reserved for the system
board.

System Rate: 1024, 2048, 4096 and 6144 Hz (binary).

The System Rate must be an integer multiple of the
Medium System Rate.

Medium System Rate: Must be an integer multiple of the
Low System Rate.

The Low System Rate is always set at 25.6. The Medium
System Rate is typically 256.

Low System Rate: 25.6.

Name: Describes this resource as it will appear in Station
Builder resource lists when opened against an .hwi file.

Digital Input/Digital Output icons

The name includes the connector number (for example:
“Dig In 1-J54”).

Changing this name may invalidate existing station
configurations.

Name: Describes this resource as it will appear in Station
Builder resource lists when opened against an .hwi file.

Analog Output icons

Connector: Both Analog Outputs are available on the
“DA Output” connector (located on the front of the 494.04
chassis).

Changing this name may invalidate existing station
configurations.

Name: Describes this resource as it will appear in Station
Builder resource lists when opened against an .hwi file.

Hydraulic Interface icon (HPU)

Changing this name may invalidate existing station
configurations.

Connector: J25.

HPU with HSM: True: Indicates the system’s HPU
supplies HSMs. False: used for HPU only systems
(makes the HPU selection available to Station Builder).

36 MTS Series 793 Utility Software

HWI Hardware Settings