Rockwell Automation 1512A MV Controllers - 800A One-High Cabinet User Manual

Page 102

Advertising
background image

C-4

ArcShield Chimney Installation Instructions

1512A-UM102B-EN-P – June 2013


Cabinet Preparation

In preparation for mounting a chimney, remove ¼ -20 fasteners from the

Relief vent on the top of the MV enclosure. Leave the (4) corner

fasteners in place. (See Figure B.6)

Remove Fasteners

Relief Vent

Do not remove

(4) corner

fasteners

Figure C.3 – Relief Vent Fasteners (top view)

Figure C.4 – Relief Vent

The chimneys are designed to fit over the fastener heads at the (4) corners

of the Relief vent. The corner fasteners are required to secure the Relief
vent during installation.