Rockwell Automation 1512A MV Controllers - 800A One-High Cabinet User Manual

Page 43

Advertising
background image

4-4

Common Installation

1512A-UM102B-EN-P – June 2013

A T T E N T I O N

A T T E N T I O N

To avoid shock hazards, lock out incoming power (see
page 5-3) before working on the equipment. Verify

with a hot stick or appropriate voltage measuring

device that all circuits are voltage free. Failure to do so

may result in severe burns, injury or death.

Incoming cables are connected to the power bus in the last section on the

left.

I M P O R T A N T

I M P O R T A N T

For Non-ArcShield units, incoming line cable size
should not exceed 1-750 MCM or 2-500 MCM per

phase.

For ArcShield units, incoming line cable size should

not exceed 1-500 MCM or 2-4/0 per phase.
For larger cables, an incoming line module must be

used for either cabinet styles.

1) Remove the center-back plate or side plate to access the power bus. If

access to the rear of the unit is not possible, refer to Accessing the Power
Bus for either Standard or ArcShield enclosure.

2) Connect the incoming power lines to the power bus. Torque to

specifications (see page 1-3) (Figure 4.4).

Figure 4.4 – Incoming Line Cable Connections, Typical

I M P O R T A N T

I M P O R T A N T

If line cables require installation by front access,

complete the incoming line connection before
installing load cables.

3) Connect the ground wire to the ground bus lug.

Incoming Line Cable

Connections