Maintenance 5-21

1512A-UM102B-EN-P – June 2013

The interlocking mechanism of the medium voltage starter is designed

to prohibit access to the power cell while the isolation switch handle is

in the ON position and the isolation switch is closed.

The following procedure is intended to be used only

when the isolation switch cannot be opened as de-

scribed in the Door Opening Procedure (page 2-1).

This procedure may expose personnel to energized

medium voltage components. Whenever possible,

lock out incoming power before beginning this

procedure. If you are unable to lock out incoming

power, use the appropriate protective equipment and

work practices to avoid shock hazards. Failure to do

so may result in severe burns, injury or death.

1) Remove the two 1/4-20 self-tapping screws from the Z-clip and

remove the Z-clip.

Figure 5.18 - Z Clip

2) Remove the two door locking bolts.

3) Use a flat-headed screwdriver to turn the defeater pin on the right

side of the isolation switch handle (see Figure 5.17).

4) Open the power cell door.

Emergency Circumvention

Procedure for Power Cell Entry

I M P O R T A N T

I M P O R T A N T

A T T E N T I O N

A T T E N T I O N