A-4

ArcShield Unit Information

1512A-UM102B-EN-P – June 2013

23 [584]

25 [633]

Figure A.2 – Cross-section of plenum extension, dimensions in inches [mm].


The following options for locating the plenum exhaust are presented:

1. Plenum ducted to an area of the control room where arc gases are

permitted to escape, with plenum extensions (see Figures 4 and 5).

2. Plenum duct to outside of control room (see Figures 6 and 7).

Plan the location where the plenum will exhaust. Ensure that:

There is no access to personnel while equipment is energized.

Area is free of flammable material or vapors

Ensure that adequate space is provided around the plenum exhaust, as

outlined in Figures A.3 through A.6.

I M P O R T A N T

I M P O R T A N T

Be aware that equipment in the area of the plenum

exhaust point will be damaged or destroyed.


Plenum