Rockwell Automation 1512A MV Controllers - 800A One-High Cabinet User Manual
Page 78
A-4
ArcShield Unit Information
1512A-UM102B-EN-P – June 2013
23 [584]
25 [633]
Figure A.2 – Cross-section of plenum extension, dimensions in inches [mm].
The following options for locating the plenum exhaust are presented:
1. Plenum ducted to an area of the control room where arc gases are
permitted to escape, with plenum extensions (see Figures 4 and 5).
2. Plenum duct to outside of control room (see Figures 6 and 7).
Plan the location where the plenum will exhaust. Ensure that:
There is no access to personnel while equipment is energized.
Area is free of flammable material or vapors
Ensure that adequate space is provided around the plenum exhaust, as
outlined in Figures A.3 through A.6.
I M P O R T A N T
I M P O R T A N T
Be aware that equipment in the area of the plenum
exhaust point will be damaged or destroyed.
Plenum