Installation Standard Enclosure 2-5

1512A-UM102B-EN-P – June 2013









Joining Sections

Note: Joining hardware can be found in a package mounted to the
front of the shipping skid. Refer to publication MV-QS050_-EN-P for

level floor surface requirements.

1) Position the left side section on a level surface and secure the

section in place with ½ in. (M12) floor mounting bolts (Refer to

Anchoring, page 2-4).

2) When joining NEMA/EEMAC Type 12 sections, apply a

continuous 1/8-in.- (3-mm-) wide bead of silicon sealer around the

perimeter of one section.

3) Remove the side bus access covers if applicable.
4) Position the right section against the left section. Ensure that the

surface is level.

5) Secure the sections together using the 1/4-20 self-tapping screws.

Thread the screw through the 0.281 in. clearance hole to the

corresponding 0.219 in. pilot hole. To access the front clearance

holes of the left-side cabinet, open the medium voltage doors. To

access the rear clearance holes remove the rear covers of the starter.
If rear access is not available, refer to Access to the Power Bus –

Front Access, page 2-9.

6) Secure the right section to the floor using ½ in. (M12) floor

mounting bolts (refer to Anchoring, page 2-4).