Rockwell Automation 1512A MV Controllers - 800A One-High Cabinet User Manual

Page 19

Advertising
background image

Installation Standard Enclosure 2-9

1512A-UM102B-EN-P – June 2013

Bus access barriers

Remove self-tapping

screws from bus access

barriers

Figure 2.8 – Low Voltage Panel

5) Use a flat head screwdriver and turn both of the ¼ turn fasteners 180

degrees in a counterclockwise direction.

6) Pull on right-hand side of low voltage panel. Swing low voltage panel

to the front and left of cabinet (see Figure 2.9).

Note: The power cell door must be in a fully opened position prior to

rotating the low voltage panel.


7) Locate the removable bus access barriers.
8) Remove retaining screws from removable bus access barriers to

expose incoming cable connections to main bus (see Figure 2-9).

9) Install incoming line cables to power bus, torque to specifications

(see page 1-3).

10) Reverse procedure after cables have been installed.