Maintenance 5-9

1512A-UM102B-EN-P – June 2013

Removing the Contactor

To avoid shock hazards, lock out incoming power

(see page 5-3) before working on the equipment.

Verify with a hot stick or appropriate voltage

measuring device that all circuits are voltage free.

Failure to do so may result in severe burns, injury

or death.

1) Complete the Power Lockout Procedure (see page 5-3).
2) Disconnect the control wiring harness from the wire plug at the

lower left side of the contactor (See Figure 5.6)

3) Use a 9/16 in. socket wrench to disconnect the power cables from

the rear of the contactor.

4) Remove the nylon contactor bushing retaining screw from the con-

tactor interlock lever.

5) Slide the contactor interlock rod and the nylon contactor bushing

out of the groove in the contactor interlock lever (see Figure 5.7).

A T T E N T I O N

A T T E N T I O N

Figure 5.7 - Removing the Contactor (Front View)