Access to power bus (cont.) – Rockwell Automation 1512A MV Controllers - 800A One-High Cabinet User Manual

Page 34

Advertising
background image

Installation – Arc Resistant (ArcShield) 3-9

1512A-UM102E-EN-P – June 2013

Side Access

A side bus access cover is located on each side of the controller, when

required.

1) Remove the hardware from the appropriate side bus access cover.
2) Remove the side bus access cover (Figure 3.6)
3) ArcShield units at the end of a line-up have a ground connection to the

inner plate of the side bus access cover (see Figure 3.7 and 3.8). This
connection must be maintained to ensure unit arc resistant

performance.











Figure 3.7 – ArcShield Side Bus Access Cover Warning Label

Access to Power Bus
(cont.)