Rockwell Automation 1512A MV Controllers - 800A One-High Cabinet User Manual

Page 93

Advertising
background image

ArcShield Plenum Installation Instructions B-11

1512A-UM102B-EN-P – June 2013

STEP 4 – Closing the Front of the Plenum Sections

After the first stage of the Plenum assemblies have been mounted, the
Plenums can then be “closed-up” by replacing the front duct sections as

shown in figure B.10 to B.12.

Top Plate

Bottom Plate

Front Closing

Plate

Figure B.10

Figure B.11

Figure B.12


I M P O R T A N T

I M P O R T A N T

Do not re-install the front duct section of the last

Plenum on the exhaust side of the Line-up at this
time. (Refer to Step 6 for more information)

NOTE: Use silicone caulking generously to fill any air gaps once the

Plenum has been securely mounted in place.

Advertising