ArcShield Plenum Installation Instructions B-5

1512A-UM102B-EN-P – June 2013

An example of a general Plenum assembly configuration is shown in

Figure B.3. Plenums of varying widths are mounted directly over the MV
enclosures of the corresponding width. A 36-inch Exhaust extension

assembly is shown mounted on the extreme right side Plenum of the

equipment “Line-up” (can alternatively exhaust to the left).

Sealed end

36” Exhaust extension

Exhaust end

Figure B.3 – ArcShield Line-up


Plenum exhaust can be on the left or right hand end of the line up.

Pictures and figures in this procedure are shown for a right hand exhaust

exit direction. Also shown is an optional vertical (top) direction exhaust
extension. (See Figure B.17)

I M P O R T A N T

I M P O R T A N T

Plenum components not directly mounted to the

tops of the MV enclosures, must have additional

mounting support. This includes the Extension
components and 90° Elbow Sections. (Refer to Step

7.)

General Plenum
Layout