Installation – Arc Resistant (ArcShield)

1512A-UM102B-EN-P –June 2013

Anchoring

Place the controller in the desired installation location. Use ½ in. (M12) floor

mounting bolts to securely fasten the controller to the mounting surface.

See Figure 3.4 and 3.5 as an example of the location of the mounting holes
in the cabinet.

Note: Refer to Dimension Drawing provided with order

documentation for additional details related to cabinet floor
plan.

Pre-determined cabinets have been designed for

Uniform Building Code (UBC) seismic zone 1, 2A,

2B, 3 and 4, and IBC (International Building Code) seismic activity

without overturning or lateral movement, provided they are securely

mounted according to UBC, IBC and local building codes. This can

include concrete pad design, steel floor design and the sizing of cabinet

anchors. Concrete floor cutouts must not be adjacent to floor anchor

bolts and must be sized to seismic load. Consult factory if floor mounting

must be reviewed by an accredited engineer. Many jurisdictions require

an engineer from the local area to review the design. Seismic qualification

does not indicate that the equipment will function properly after a

seismic event.