Chapter

2

1512A-UM102B-EN-P – June 2013

Installation – Standard Enclosure

I M P O R T A N T

I M P O R T A N T

For installation of ArcShield equipment refer to

Chapter 3.

I M P O R T A N T

I M P O R T A N T

For information on the installation site preparation,

see

General Handling Procedures for MV Products,

Publication MV-QS050_-EN-P.

A T T E N T I O N

A T T E N T I O N

Use suitable personal protective equipment (PPE)
per local codes or regulations. Failure to do so may

result in severe burns, injury or death.



Door Opening Procedure

Opening the Low Voltage Doors

Low voltage door is identified as LV in Figure 2.1.

1) To access the low voltage compartment, use a flat-head screwdriver

and turn both of the 1/4-turn fasteners, located on the low voltage

door, 90° in a counterclockwise direction.

2) The door is now released and will swing open.

3) Reverse the procedure to secure the door.













.

MV

LV

MV

¼-turn Fasteners for

Upper Low Voltage Door

MV

.

.

.

.

.

.

.

.

MV

LV

MV

¼-turn Fasteners for

Upper Low Voltage Door

MV

.

.

.

.

.

.

.