ArcShield Plenum Installation

Instructions

The following instructions are provided to ensure the proper installation

and function of plenum components supplied with ArcShield enclosures.
Refer to Appendix A for additional information related to ArcShield

plenums before attempting to follow these instructions.


Recommended Torque Values

1/ 4 -20 Thread Fasteners – 6 ft-lb (7.5 N·m)

5 /16 -18 Thread Fasteners – 11 ft-lb (14 N·m)

Plenum Bracing

Bracing of the plenum must be able to withstand the dynamic forces of
the arc fault as well as any other vibration or seismic effects associated

with the installation. Most of this force will be in the direction opposite

to where the relief vent exits. The amount of bracing will depend on how
the plenum is supported at its exit as well as the distance from the end of

the cabinets to the exit vent.

• A flange is available for installing hangers for supporting the weight

of the plenum.

• The plenum extension has holes for mechanical support.

• Weight per unit length of Rockwell supplied plenum =19 lb/ft [28

kg/m].

• Installer is responsible for ensuring that the plenum extension has

sufficient support to resist the effect of vibrations and seismic effects.

Plan the location where the plenum will exhaust

(refer to Appendix A). Be aware that equipment

in the area of the plenum exhaust will be damaged
or destroyed. The plenum exhaust area is to be

marked as a Hazardous Zone, and labeled per

Figure B.1.