Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 100

Advertising
background image

100

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

Appendix A PowerMonitor 1000 Data Tables

Table 42 - Unit Run Status Results Parameters

CSP File No.

N28

CIP Instance

21

Applies to

All models

No. of Elements

25

No. of Words

25

Data Type

Integer

Data Access

Read

Table 43 - Unit Run Status Results

Element

No.

Modbus

Address

Element Name

Range

Description

0

30901

Bulletin Number

1408

Always returns 1408

1

30902

Series Letter

0…8

Indicates the unit hardware series letter, for example.

0 = A

1 = B

.

.

8 = H

2

30903

Catalog Device Type

0…4

The catalog number type of this device.

0 = TR1

1 = TR2

2 = EM1

3 = EM2

4 = EM3

3

30904

Communication Type

0…1

The communication type of this device

0 = Serial only

1 = both serial and Ethernet

4

30905

Application FRN

-

The current firmware revision

5

30906

Boot Code FRN

-

The current boot code revision

6

30907

Default Device ID

1…247

A semi-unique number assigned to a device at the time

it is manufactured. Used for out of the box

communication over DF1 and Ethernet.

7

30908

Accuracy Class

0…3

Indicates the revenue metering accuracy class of the

power monitor as it is shipped from the factory.

0 = No Class Designation

1 = Class 1

2 = Class 0.5

3 = Class 0.2

8

30909

Overall Status

0…16383

0 indicates normal operation. Each bit indicates a

different fault condition.

Bit 0 = Flash Memory

Bit 1 = SRAM

Bit 2 = NVRAM

Bit 3 = SPI Interface

Bit 4 = Real Time Clock

Bit 5 = Watchdog Timer

Bit 6 = Metering

Bit 7 = LCD Interface

Bit 8 = Serial Communications

Bit 9 = Ethernet Communications

Bit 10 = Error Log Full