Chapter 2 PowerMonitor 1000 Unit Features

Energy results (kWh, kVARh, and kVAh) roll over to 0 at a value of
9,999,999,999,999 or 10

12

-1.

Setup

Only basic analog input setup is required for energy metering.

Results

Energy metering results may be viewed using the following methods:

Web interface

LCD screen

Communication

Energy results are not available via the HyperTerminal communication tool.

Commands

The following commands are supported by the power monitor:

Set GWh/kWh register

Set GVARh/kVARh register

Set GVAh/kVAh register

Clear all energy registers

Related Functions

KYZ output

Energy log

Configuration lock

Demand Metering

Demand is an electric power term that expresses the average energy usage over a

period of time. The power monitor may be configured to measure demand using

a fixed demand period or a sliding window. The demand period may be timed

internally, synchronized to an external demand end-of-interval contact connected

to the S2 status input, or synchronized using communication.

This function applies to catalog numbers 1408-EM2 and 1408-EM3.