5 - explicit messaging, Explicit message setup – examples, Chapter 5 – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 53: Explicit messaging, Chapter

Advertising
background image

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

53

Chapter

5

Explicit Messaging

This section discusses data retrieval and parameter configuration using explicit

messaging from Rockwell Automation controllers. Explicit messaging allows you

to read and write from a controller to specific data tables within the power

monitor. With explicit messages, users can read real-time power and energy

values, configure analog input parameters, configure communication parameters,

and also read energy logs.

In general, these instructions apply to Ethernet network communication

(Ethernet/IP protocol) and Serial communication (DF1 half-duplex or full-

duplex or DH485 protocols), provided that the protocol is supported by the

controller. If using serial communication, the controller serial port must be

correctly configured for protocol, communication rate, or parity. Refer to the

appropriate controller user documentation for further details.

Please refer to

Appendix A

, PowerMonitor 1000 Data Tables for descriptions of

the power monitor data tables and their data access privileges, and data types.

The power monitor allows PLC-5 Typed, SLC Typed, and CIP Generic message

requests.

Explicit Message Setup –

Examples

This section gives examples on how to set up explicit messaging.

Read/Write Single or Multiple Elements

You can perform single or multiple element reads and writes to the power

monitor. Below is a table documenting the message type to use for specific read/

write type and communication scenarios.

IMPORTANT

When performing a write to the power monitor, you must write

the password value to the password element of that specific

data table that you are writing to. This must be done in the

same message; therefore you must perform a multiple element

write. If you wish to perform only a single element write, you

must write the password value to the Single Element Password

Write table. This allows you to perform writes to any write

access data table for the next 30 minutes.

Advertising
This manual is related to the following products: