18

30137-38

Current Phase 3

Magnitude

Amperes

0…9,999,999

Shows the present magnitude of this

phase.

19

30139-40

Degrees out of

range

0…360

When Status = 5, how many degrees

out of range.

20

30141-42

Reserved

0

Reserved for future use

Table 26 - Wiring Diagnostics Results

Element

No.

Modbus

Address

Element Name

Units

Range

TR1

TR2

EM1

EM2

EM3

Description

Table 27 - Volts, Amps, Frequency Results Parameters

CSP File No.

F21

CIP Instance

14

No. of Elements

16

No. of Words

32

Data Type

Float

Data Access

Read

Table 28 - Volts, Amps, Frequency Results

Element

No.

Modbus

Address

Element Name

Range

TR1

TR2

EM

1

EM

2

EM

3

Description

0

30201-2

L1 Current

0.000…9,999,999

Phase 1 scaled RMS Current

1

30203-4

L2 Current

0.000…9,999,999

Phase 2 scaled RMS Current

2

30205-6

L3 Current

0.000…9,999,999

Phase 3 scaled RMS Current

3

30207-8

Average Current

0.000…9,999,999

Average RMS Current

4

30209-10

L1-N Volts

0.000…9,999,999

Phase 1 scaled RMS Voltage

5

30211-12

L2-N Volts

0.000…9,999,999

Phase 2 scaled RMS Voltage

6

30213-14

L3-N Volts

0.000…9,999,999

Phase 3 scaled RMS Voltage

7

30215-16

Average L-N Volts

0.000…9,999,999

Averaged RMS Voltage

8

30217-18

L1-L2 Volts

0.000…9,999,999

Line 1 to Line 2 Volts

9

30219-20

L2-L3 Volts

0.000…9,999,999

Line 2 to Line 3 Volts

10

30221-22

L3-L1 Volts

0.000…9,999,999

Line 3 to Line 1 Volts

11

30223-24

Average L-L Volts

0.000…9,999,999

Average Line to Line Volts

12

30225-26

Frequency

40.0 Hz…70.0 Hz

Last frequency reading.

13

30227-28

Percent Current

Unbalance

0.0…100.0

Percent maximum deviation from Ave.

/ Ave.

14

30229-30

Percent Voltage

Unbalance

0.0…100.0

Percent Maximum deviation from Ave.

/ Ave.

15

30231-32

Metering Iteration

0…9,999,999

Increments by 1 for each new

metering calculation.

Advertising
This manual is related to the following products: