Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 83

Advertising
background image

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

83

PowerMonitor 1000 Data Tables Appendix A

Table 18 - Command Table

Element

No.

Modbus

Address

Element Name

Default

Value

Range

TR1

TR2

EM

1

EM

2

EM

3

Description

0

40601-2

Password

0

0…9999

When writing the complete table this

parameter allows the input data to be

accepted. When writing a single parameter

the separate password table should be used.

Returns -1 on a read.

1

40603-4

Command Word 1 0

0…32

These commands can be sent to the power

monitor. When using the optional elements

the command table must be sent complete

with all elements present. If the single

password table is used to gain access to

configuration items then the command can

be sent alone without optional settings. The

command options are:
0 = No Action

1 = Set kWh Register

2 = Set kVARh Register

3 = Set kVAh Register

4 = Clear All Energy Registers

5 = Set Status 1 Count

6 = Set Status 2 Count

7 = Clear Energy Log

8 = Force KYZ Output On

9 = Force KYZ Output Off

10 = Remove Force from KYZ

11 = Restore Factory Defaults

12 = Perform Wiring Diagnostics

13 = Reset power monitor System

14…32 = Reserved

If a command is received that is not

supported by your catalog number the

command will be ignored.

2

40605-6

Command Word 2 0

0…32

0 = No Action

1 = Clear Min/Max Records

2 = Store and clear current Load Factor

Record

3 = Clear Load Factor Log

4 = Store and clear current TOU Record

5 = Clear TOU Log

6 = Clear Error Log command

7 = Troubleshooting Mode Enable

8…32 = Reserved.

If a command is received that is not

supported by your catalog number the

command will be ignored.

3

40607-8

Clear Single Min/

Max Records

0

0…35

0…31

0…19

When setting the Min/Max Clear bit this

value can be sent to specify a single

parameter. If clearing all values this is not

required.
EM3 = 0…35

TR2 = 0…31

TR1 = 0…19

0=Clear All Parameters

1= Clear the 1st Min/Max Record

2= Clear the 2nd Min/Max Record

35=Clear the 35th Min/Max Record