PowerMonitor 1000 Data Tables Appendix A

Table 6 - Advanced Configuration Parameters

CSP File No.

F11

CIP Instance

4

No. of Elements

22

No. of Words

44

Data Type

Float

Data Access

Read/Write

Table 7 - Advanced Configuration

Element

No.

Modbus

Address

Range

Element

Name

Default

Value

Range

TR1

TR2

EM1

EM2

EM3

Description

0

40101-2

Password

0

0…9999

When writing the complete table this

parameter allows the input data to be

accepted. When writing a single parameter the

separate password table should be used.

Returns -1 on a read.

1

40103-4

New Password 0

0…9999

This becomes the new password when the

proper the configuration password entry has

been made and this parameter is greater than (-

1).

2

40105-5

Metering

Result

Averaging

1

0…1

The metering results for volts, amps, power and

frequency is averaged over 8 cycles of data to

provide a steady output reading.
0 = Off

1 = On

3

40107-8

Log Status

Input Changes

0

0…1

0 = Disable recording of status input changes

into the status log.

1 = Enable recording of status input changes

into the status log.

4

40109-10

Use Daylight

Savings

Correction

0

0…1

0 = Disable Daylight Savings

1 = Enable Daylight Savings

5

40111-12

Daylight

Savings

Month/Week/

Day Start

030201
March, 2nd,

Sunday

10101…

120507

This is the day that the power monitor will add

an hour to the time. This feature also looks at

Ethernet SNTP offset and corrects for Daylight

Savings.
Example: 040107 = April/1st week/Sunday
Month Settings:

01 = January…12 = December
Week Settings:

01 = 1st week…05 = Last Week
Day of the Week Settings:

01 = Sunday…07 = Saturday

6

40113-14

Hour of Day

Start

2

0…23

The hour of day the daylight savings

adjustment should be made to add an hour.