Operation, Setup, Commands – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 44: Related functions, Status inputs

Advertising
background image

44

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

Chapter 2 PowerMonitor 1000 Unit Features

Operation

The KYZ output can operate in any of the following modes:

Energy pulse operation with fixed pulse width or toggle

Forced operation

Setup

KYZ-output set-up parameters are found in the Advanced Setup menu and are

summarized in the table.

Commands

Force KYZ Output On

Force KYZ Output Off

Remove Force from KYZ

Related Functions

Configuration lock

Status Inputs

The power monitor has two self-powered (24V DC) status inputs. Two typical

uses for status inputs are to totalize external pulse meters and to synchronize the

demand end of interval (EOI).

This function applies to catalog numbers 1408-EM1 (except demand EOI

synch), 1408-EM2, and 1408-EM3.

Parameter

Description

Range

Default

User Setting

Model
TR1

TR2

EM1 EM2 EM3

KYZ Output

Parameter

0 = Disable

1 = Wh Fwd

2 = Wh Rev

0…2

0

3 = VARh Fwd

4 = VARh Rev

5 = VAh

0…5

KYZ Output Scale

The increase in value of the selected

parameter that caused the output to

change state

1…

100,000

1000

KYZ Pulse Duration

Setting

0 = toggle output

50…1000 = duration of output pulse,

rounded to 10 ms

0 or 50…

1000

250 ms