Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 96

Advertising
background image

96

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

Appendix A PowerMonitor 1000 Data Tables

Table 37 - Unit Status Log Codes

Status Event Type

(Decimal)

Event #

General Code (Decimal)

Code #

Information Code (Decimal)

Code #

Self Test Status

1

Pass

0

Flash Memory

1

Overall Status

1

Boot Code Checksum

2

Application Code Checksum

4

Calibration Data CRC

8

No Calibration Data

16

Wrong Application FRN

32

Invalid Model Type

64

WIN Mismatch

128

Missing Upgrade Block

256

SRAM

2

Failed Read/Write Test

1

NVRAM

4

Failed Read/Write Test

1

SPI Interface

8

SPI Device Not Responding

1

SPI Interface Failed

2

Real Time Clock

16

Real Time Clock Failed

1

Real Time Clock not Set

2

Watchdog Timer

32

Watchdog Time Out

1

Metering

64

Metering Status Failed

1

LCD Interface

128

LCD Interface Failure

1

Serial Communications

256

Serial Communication Port Failed

1

Ethernet Communications

512

Ethernet Communications Port Failed

1

Modbus Stack Initialization Failed

2

Demand Broadcast Thread Init Failed

4

SNTP Thread Init Failed

8

Input Over Range

1024

Input Over Range Voltage

1

Input Over Range Current

2

Voltage Phase Loss

2048

Voltage Channel 1 Loss

1

Voltage Channel 2 Loss

2

Voltage Channel 3 Loss

4

Process Error

4096

Advertising
This manual is related to the following products: