Appendix A PowerMonitor 1000 Data Tables

Table 38 - Energy Log Results Parameters

CSP File No.

F26

CIP Instance

19

No. of Elements

21

No. of Words

42

Data Type

Float

Data Access

Read

Table 39 - Energy Log Results

Element

No.

Modbus

Address

Element Name

Range

TR1

TR2

EM1

EM2

EM3

Description

0

30701-2

Internal Record

Identifier.

1

30703-4

Timestamp Year of

record

-

The date and time when the

record was recorded.

2

30705-6

Timestamp Month/

Day

-

3

30707-8

Timestamp Hour/

Minute

-

4

30709-10

Timestamp Seconds/
Hundredths

-

5

30711-12

Status 1 Count xM

0…9,999,999

Status 1 Count times 1,000,000

6

30713-14

Status 1 Count x1

0…999,999

Status 1 count times 1

7

30715-16

Status 2 Count xM

0…9,999,999

Status 2 Count times 1,000,000

8

30717-18

Status 2 Count x1

0…999,999

Status 2 count times 1

9

30719-20

GWh Net

+/- 0…9,999,999

Net gigawatt hours

10

30721-22

kWatth Net

+/- 0.000…999,999

Net kilowatt hours

11

30723-24

GVARH Net

+/- 0…9,999,999

Net gigaVAR hours

12

30725-26

kVARh Net

+/- 0.000…999,999

Net kiloVAR hours

13

30727-28

GVAh Net

0…9,999,999

Net gigaVA hours

14

30729-30

kVAh Net

0.000…999,999

Net kiloVA hours

15

30731-32

kWatt Demand

+/- 0.000…9,999,999

The average real power during

the last demand period.

16

30733-34

kVAR Demand

+/- 0.000…9,999,999

The average reactive power

during the last demand period.

17

30735-36

kVA Demand

0.000…9,999,999

The average apparent power

during the last demand period.

18

30737-38

Demand PF

-100.0…+100.0

The average demand for PF during

the last demand period.

19

30739-40

Reserved

0

Reserved for future use.

20

30741-42

Reserved

0

Reserved for future use.