Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 79

Advertising
background image

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

79

PowerMonitor 1000 Data Tables Appendix A

Table 13 - Date and Time Configuration Parameters

CSP File No.

N14

CIP Instance

7

Applies to

All models

No. of Elements

8

No. of Words

8

Data Type

Integer

Data Access

Read/Write

Table 14 - Date and Time Configuration

Element

No.

Modbus

Address

Element Name

Default

Value

Range

Description

0

40401

Password

0

0…9999

When writing the complete table this parameter allows the input data

to be accepted. When writing a single parameter the separate

password table should be used. Returns -1 on a read.

1

40402

Date: Year

2005

2001…

2100

The range is from 2001… 2100. A write sets the current year.

2

40403

Date: Month

1

1…12

A write sets the current month.

A read returns current month.

1=January, 2=February,…12=December

3

40404

Date: Day

1

1…31

A write sets the current day of the month.

A reads returns the current day of the month.

The internal real-time clock adjusts the date for leap-year.

4

40405

Time: Hour

0

0…23

A write sets the current hour.

A read returns the current hour.

0=12am, 1=1am,…23=11pm

The internal real-time clock does not adjust for daylight savings time.

5

40406

Time: Minute

0

0…59

A write sets the current minutes.
A read returns the current minutes.

6

40407

Time: Seconds

0

0…59

A write sets the current seconds.
A read returns the current seconds.

7

40408

Time: Hundredths

0

0…99

Set this element to 0 for writes. Returns hundredths of a second on

read.

Advertising
This manual is related to the following products: