Calculating energy log depth – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 66

Advertising
background image

66

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

Chapter 5 Explicit Messaging

Example 2: Read Min/Max Log for Average Current

This example explains how to configure the Log Request Table to read the Min/

Max log for Average Current.

Refer to Min/Max Parameter List on page 103

for the specific record to return.

In this example, Average Current is record 4.

1. Create a write message to write the following values to the Log Request

Table.

2. Create a read message to read the values in the Min/Max Log table.

Calculating Energy Log Depth

How long the Energy Log takes to fill may be as little as 288 hours or as long as

three years depending on how you configure the log rate. The Energy records

maximum depth is 17280 records that covers the following:

Status 1 and 2 counters

Real, Reactive, and Apparent Demand

Real, Reactive, and Apparent Energy

Demand Power Factor

Element

Item Name

Value

0

Selected Log

2

1

Chronology of Auto Return Data

0

2

Mix/Max Record to be Returned

4

3

Number of Unit Status Records

0

4

Number of Energy Log Records

0

5

Number of Time of Use Log Records

0

6

Number of Load Factor Log Records

0

7

Load Factor or TOU Record to be Returned

0

Advertising