Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 72

Advertising
background image

72

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

Appendix A PowerMonitor 1000 Data Tables

7

40115-16

Return from

Daylight

Savings

Month/Week/

Day

110101
November,

1st, Sunday

10101…

120507

This is the day that the power monitor will

subtract an hour from the time. This feature

also looks at Ethernet SNTP offset and corrects

for the return from Daylight Savings.
Month Settings:

01 = January…12 = December
Week Settings:

01 = 1st week…05 = Last Week
Day of the Week Settings:

01 = Sunday…07 = Saturday

8

40117-18

Hour of Day

End

2

0…23

The hour of day the daylight savings

adjustment should be made to subtract an hour.

9

40119-20

KYZ Solid

State Output

Parameter

0

0…5

The parameter selected will pulse the KYZ

output at a rate that equals the parameter

value divided by KYZ scale.
0 = Disable

1 = Wh Fwd

2 = Wh Rev

3 = VARh Fwd (EM2 and EM3 Only)

4 = VARh Rev (EM2 and EM3 Only)

5 = Vah (EM2 and EM3 Only)

10

40121-22

KYZ Solid

State Output

Scale

1,000

1…

100,000

The KYZ output parameter divided by the scale

is the output pulse rate. Example: Wh is

selected for the parameter and 1,000 is the

scale value. The output is pulsed every kWh.

11

40123-24

KYZ Pulse

Duration

Setting

250 ms

0 or

50…1000

Set as 50…1000 to indicate the duration of the

pulse in milliseconds, or set to 0 for KYZ-style

transition output. (Toggle)

The value for delay is rounded off to the

nearest 10ms internally during this function.

12

40125-26

Status Input 1

Input Scale

1

1…

1,000,000

When a status pulse is received the count is

increased by the scale factor. Input pulse *

input scale added to total status count.

13

40127-28

Status Input 2

Input Scale

1

1…

1,000,000

When a status pulse is received the count is

increased by the scale factor. Input pulse *

input scale added to total status count.

14

40129-30

Demand

Source

0

0…3

When item Demand Broadcast Master Select

of the ethernet table is set to master a

selection of 0 through 2 sets the type of master

input. In this case item 3 is ignored. When the

Demand Broadcast Master Select of the

ethernet table is set to slave then any of these

inputs can set the end of the demand period.

Selections of 0 through 2 can be selected for

RS485 units.
0 = Internal Timer

1 = Status Input 2

2 = Controller Command

3 = Ethernet Demand Broadcast
Selection 3 can only be programmed when the

Ethernet option is installed.

Table 7 - Advanced Configuration

Element

No.

Modbus

Address

Range

Element

Name

Default

Value

Range

TR

1

TR

2

EM

1

EM

2

EM

3

Description