PowerMonitor 1000 Overview Chapter 1

Troubleshooting mode lets you enter a password-protected command that

promotes your PowerMonitor unit to an EM3 model. This makes all measured

parameters available for troubleshooting purposes.

Communication Overview

All PowerMonitor 1000 units come standard with an RS-485 serial

communication port. Models with catalog numbers ending in -ENT are

equipped with an Ethernet 10BaseT communication port. This section covers

serial and Ethernet communication, the available protocols, and what protocols

to use for your application.

What Can I Do Using Communication Networks?

When you use communication networks with the power monitor you can do the

following things.

Configure analog input parameters such as PT/CT ratios

Configure communication parameters such as IP address

Read real-time power and energy data

Read energy logs

Serial Communication

The RS-485 serial communication port allows serial communication to your

power monitor. This port can be configured to communicate using the protocols

listed the this table.

Min / max log

Load factor log

Time of use logs

Status log

Measured Parameters

TR1

TR2

EM1

EM2

EM3

Protocol

Applications

DF1 Half-duplex Slave

The DF1 Half-duplex Slave protocol may be used for point-to-point or multi-drop communication

using a DF1 Polling Master driver for RSLinx software, or when using explicit messages from

Rockwell Automation controllers communicating via DF1 Half-duplex Master.

DF1 Full-duplex

The DF1 Full-duplex protocol may be used only for point-to-point communication using a RS-232

DF1 driver for RSLinx software, or when using explicit messages from Rockwell Automation

controllers communicating via DF1 Full-duplex.

Modbus RTU Slave

The Modbus RTU Slave protocol may be used for point-to-point or multi-drop communication with

a client using the Modbus RTU Master protocol for PLC controller communication.

Auto-sense

With auto-sense selected, the RS-485 port switches among the available serial protocols based

on the format of the packets the port receives.

DH485

The DH485 protocol may be used for point-to-point or multi-drop communication using a 1747-

PIC/AIC+ driver for RSLinx software, or when using explicit messages from Allen-Bradley

controllers or HMI (PanelView) terminals communicating via DH485.