PowerMonitor 1000 Unit Features Chapter 2

Metered Parameters

The power monitor calculates and returns four-quadrant power measurements

including these:

L1, L2, L3 and Total True Power Factor, percent lagging (-) and leading

(+)

L1, L2, L3 and Total Real Power, kW

L1, L2, L3 and Total Reactive Power, kVAR

L1, L2, L3 and Total Apparent Power, kVA

Only total three-phase power results are provided when Direct Delta or Open

Delta wiring modes are selected.

The

Magnitude and Direction of Power Quantities

chart indicates the

relationship between the magnitude and direction of the power quantities and

the numeric signs used by the power monitor.

Figure 6 - Magnitude and Direction of Power Quantities

Setup

Only basic analog-input setup is required for power metering.

II

III

IV

I

90°

180°

270°

Pf = 100%
+kW (import)
kWH-F
(forward)

(power factor lagging)
(-)

Pf = 0
+kVAR (import)
kVARHR-F (forward)

(power factor
leading)
(+)

(power factor
lagging)
(-)

(power factor
leading)
(+)

Pf = 0
-kVAR (export)
kVARHR-R (reverse)

Pf = 100%
-kW (export)
kWH-R (reverse)