Appendix A PowerMonitor 1000 Data Tables

Table 29 - Power Results Parameters

CSP File No.

F22

CIP Instance

15

No. of Elements

17

No. of Words

34

Data Type

Float

Data Access

Read

Table 30 - Power Results

Element

No.

Modbus

Address

Element Name

Range

TR1

TR2

EM1

EM2

EM3

Description

0

30301-2

L1 True Power Factor -100.0…+100.0

Percent ratio between power and

apparent power. The value is signed

to (+) leading and (-) lagging.

1

30303-4

L2 True Power Factor -100.0…+100.0

2

30305-6

L3 True Power Factor -100.0…+100.0

3

30307-8

3 Phase True Power

Factor

-100.0…+100.0

4

30309-10

L1 kWatts

+/- 0.000…9,999,999

Line 1 kWatts

5

30311-12

L2 kWatts

+/- 0.000…9,999,999

Line 2 kWatts

6

30313-14

L3 kWatts

+/- 0.000…9,999,999

Line 3 kWatts

7

30315-16

Total kWatts

+/- 0.000…9,999,999

Total kWatts

8

30317-18

L1 kVAR

+/- 0.000…9,999,999

Line 1 kVAR

9

30319-20

L2 kVAR

+/- 0.000…9,999,999

Line 2 kVAR

10

30321-22

L3 kVAR

+/- 0.000…9,999,999

Line 3 kVAR

11

30323-24

Total kVAR

+/- 0.000…9,999,999

Total kVAR

12

30325-26

L1 kVA

0.000…9,999,999

Line 1 kVA

13

30327-28

L2 kVA

0.000…9,999,999

Line 2 kVA

14

30329-30

L3 kVA

0.000…9,999,999

Line 3 kVA

15

30331-32

Total kVA

0.000…9,999,999

Total kVA

16

30333-34

Metering Iteration

0…9,999,999

Increments by 1 for each new

metering calculation.

IMPORTANT

Only total power values are returned in delta wiring modes.

Zeroes are returned for individual phase values.