Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 105

Advertising
background image

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

105

PowerMonitor 1000 Data Tables Appendix A

9

31119-20

Peak Demand kVA

0.000…

9,999,999

The largest magnitude demand for kVA that

occurred over all of the demand intervals

since the last clear command or auto-clear

day.

10

31121-22

Average Demand

kVA

0.000…

9,999,999

A running average of demand for kVA from

the end of each demand period since the

last clear command or auto-clear day.

11

31123-24

Load Factor kVA

0…100%

Average Demand kVA / Peak Demand kVA.

This is a demand management metric that

indicates how ‘spiky’ (or ‘level’) a load is

over a period of time (usually 1 month). A

value approaching 100% indicates a

constant load.

12

31125-26

Reserved

0

Reserved for Future Use

13

31127-28

Reserved

0

Reserved for Future Use

Table 48 - Load Factor Log Results

Element

No.

Modbus

Address

Element Name

Range

TR1

TR2

EM1

EM2

EM3

Description