C - specifications, Technical specifications, Appendix c – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 125: Specifications, Appendix

Advertising
background image

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

125

Appendix

C

Specifications

Technical Specifications

Table 62 - Technical Specifications - 1408-TR1A-xxx, 1408-TR2A-xxx,

1408-EM1A-xxx, 1408-EM2A-xxx, 1408-EM3A-xxx

Attribute

Accuracy in % of Reading at 25 °C (77 °F) 50/60 Hz Unity
Power Factor

Nominal / Range

Applies to

TR1

TR2

EM1

EM2

EM3

Voltage sense

inputs: V1, V2, V3

±0.5%

X

X

X

Line-neutral rms:

347V / 15…399V

Line-line rms:

600V / 26…691V

Current sense

input: I1, I2, I3

±0.5%

X

X

X

5A / 0.05…10.0A rms

Frequency

±0.05 Hz

X

X

X

50 or 60 Hz /

40…75 Hz

Power functions:

kW, kVA, kVAR

EN62053-

21:2003

Accuracy

Requirement

Class 1

(1)

(1) Fast transient external influence tested at 2 kV.

X

X

Demand

functions: kW,

kVA

X

X

Energy functions:

kWH, kVAH

kWh

only

X

X

Metering update

rates

100 mS V, I, Hz

200 mS Power

X

X

X

X

X

Advertising